IO-Link Master Modul
IOL4A4B
|
|
Simple connection for any Ethernet protocol.
Different variants for the EtherNet/IP, EtherCAT and PROFINET protocols with 4 Class A and 4 Class B ports.Existing field devices that send classic switching signals can also be operated in SIO mode via the Class A ports.
| Mechanical | |
|---|---|
| Dimension | 205 mm x 60 mm x 34 mm |
| Working temperature | -25 °C ... 70 °C |
| Storage temperature | -40 °C ... 85 °C |
| Protection level |
IP67 |
| Connection types |
M12 connector |
| Weight | 515 gr |
| Electrical | |
|---|---|
| Total amperage | 12 A |
| Interfaces |
IO-Link EtherNet/IP EtherCAT PROFINET IO |
Simple connection for any Ethernet protocol.
- Variants for any Ethernet network: PROFINET, EtherNet/IP oder EtherCAT
- 4 IO-Link Ports Class A: for IO-Link communication and/or for digital inputs/outputs (SIO mode)
- 4 IO-Link Ports Class B: for IO-Link communication with additional power supply for energy-intensive actuators
- Support for all common transmission speeds: 4.8 kBit/s (COM1), 38.4 kBit/s (COM2) and 230.4 kBit/s (COM3).
- Robust aluminum alloy housing with protection class IP67 and a temperature range of -40 °C ... +85 °C enables reliable use even in wet areas.
M8 Connector with cable ,
Preassembled cable set
Male connector 4-pin
0,14 mm2
↓
Male connector 8-pin PUR Ø 4,8 mm ± mm0,14 mm2
05.00.60M1.J577.002M
01
Innovative new fastening system for elevator construction
Kübler Group
02
Innovative new fastening system for elevator construction
Kübler Group
03
How to install the Ants Shaft Copying System
Kübler Group
04
Concept Study: electronic overspeed governor
Kübler Group
05
Concept Study: electronic overspeed governor
Kübler Group
06
Interlift 2025 – Kübler Solutions for Smart Elevators
Kübler Group
07
Portfolio Overview: Shaft Copying Sensors
Kübler Group
Due to a technical problem, our website is only available to a limited extent. This also affects our download service area. We are already working on the solution and ask for your understanding.